Abstract
A systematic procedure in which digital signal processing, modal testing and finite element techniques can be used to seismically qualify Class IE equipment for use in nuclear generating stations is presented. A new method was also developed in which measured transmissibility functions and Fourier transformation techniques were combined to compute instrument response spectra. As an illustrative example of the qualification method, the paper follows the qualification of a safety related Class IE Heating, Ventilating, and Air Conditioning (HVAC) Control Panel subjected to both seismic and hydrodynamic loading conditions.
view the full text of this article (43 pages, format: PDF, size= 1225kB)